CPM601 Feature
Home monitors CPM601

Key Features

  • Rugged, compact design
  • Dual Frequency Ranges; 0.01MHz - 100MHz as well as 300MHz - 2GHz
  • Compatible with Accoustic, Ultrasonic, HFCT, TEV, Coupling Capacitors as wells as UHF Sensors
  • An interactive and comprehensive software PD Connect for reliable PD measurement and analysis
  • Gigabit ethernet copper Cat5e communication link between monitor and laptop
  • Optional rugged laptop with installed software suite
  • IP65 rated

Product Description

CPM601 Summary

CPM601

Rugged design, designed for reliability, 3 Phase synchronous UHF or HF partial discharge monitoring equipment.

CPM601 Benefits
    • Rugged sensors, monitor and laptop
    • Gigabit ethernet communication between monitor and laptop
    • Enhanced noise rejection
    • Realtime denoisning
    • Software packed with useful tools for reliable and interactive PD measurements
    • Robust recording and analytics
    • Customizable according to customer-specific applications
    • Suitable for Online or Offline PD measurements
CPM601 Applications

Detailed Overview

Rugged Monitoring presents the state of art Partial Discharge Monitor CPM601 to perform PD measurements in dual-frequency ranges; 0.01MHz - 100MHz as well as 300MHz - 2GHz. With the help of advanced electronics, embedded inside CPM601, now a user can perform PD measurement using variety of sensors without the need of using external frequency down converters. This presents All-in-One solution to perform PD measurements using Accoustic, Ultrasonic, HFCT, TEV, Coupling Capacitors as wells as UHF Sensors on all assets; GIS, Power Transformers, Rotating Machines and Power Cables.

Compact size and rugged enclosure and electronics make it portable, easy to carry and enabling the user to perform PD measurements with less hassle.

Monitor is capable of transferring the data directly to PD Connect software installed on laptop or data can be temporarily stored (optional) in the device enabling the user to record PD pulses with higher sampling rate. Thousands of pulses per second can be transferred to the laptop enabling the user to generate fast and reliable Phase Resolved Partial Discharge (PRPD) graphs. PRPD patterns help the user to identify type of PD. Monitor and Software are packed with all necessary tools that help to perform active PD measurements. Integrated variable amplifiers and on-board denoising features help during on-site testing in case of presence of huge noise.

There is a dedicated team for application specific customizations for sensors, monitor configuration and software integration to simplify data collection of testing and monitoring applications.

Technical Specifications

Channels8 Multiplexed (4x HF and 4x UHF)
Sampling Rate250 MS/s
Amplificationup to 50 dB, software selectable
FilteringSoftware configurable band pass filters
HF Channels Bandwidth0.01 - 100 MHz
HF Channels Sensitivity-50dBm
HF Channels Dynamic RangeDynamic Range
UHF Channels Bandwidth300 MHz - 2 GHz
UHF Channels Sensitivity-80 dBm
UHF Channels Dynamic Range70 dB
High Resolution (pulses data on simultaneous channels)10,000 pulses per second for 4 simultaneous channels
Low Resolution (pulse amplitude on simultaneous channels)50,000 pulses per second for 4 simultaneous channels
Transfer Rate400 Mbps (depending on operating system and connection)
MemorySSD up to 1 TB (Optional)
Communication Link CableCat5e
Communication Link TypeEthernet Copper
Synchronisation Inputs2 Inputs, software selectable (Internal & External)
IP RatingIP65
Ambient Temperature Rating-30C - 60C
Storage Temperature Rating-40C - 85C
Input Power45 W
Dimensions260mm(L)x310mm(W)x120mm(H)