  • Rugged, Compact Design with multiple mounting options -Din-Rail, Direct
  • 4 or 8 Synchronous Input Channels for monitoring Partial Discharge
  • Monitors Partial Discharge into the Insulation of MV/HV assets
  • Best in class EMI, ESD Immunity
  • Modbus (Serial-RS485) and Canbus integration with third party systems
  • Advance noise gating with built-in filters and software algorithms
  • Built-In Fail Safe Relay for System Failure

Product Description

PD201 Summary

PD201

Rugged design, designed for reliability, PD monitor for OEMs (Original Equipment Manufacturers) with Advance and simple integration features to third party systems/gateways.

PD201 Product Benefits
    • Rugged, Compact Design with multiple mounting options -Din-Rail, Direct
    • 4 or 8 Synchronous Input Channels for monitoring Partial Discharge
    • Monitors Partial Discharge into the Insulation of MV/HV assets
    • Best in class EMI, ESD Immunity
    • Modbus (Serial-RS485) and Canbus integration with third party systems
    • Advance noise gating with built-in filters and software algorithms
    • Built-In Fail Safe Relay for System Failure
PD201 Product Applications
    • Rugged, Compact Design with multiple mounting options -Din-Rail, Direct
    • 4 or 8 Synchronous Input Channels for monitoring Partial Discharge
    • Monitors Partial Discharge into the Insulation of MV/HV assets
    • Best in class EMI, ESD Immunity
    • Modbus (Serial-RS485) and Canbus integration with third party systems
    • Advance noise gating with built-in filters and software algorithms
    • Built-In Fail Safe Relay for System Failure

Detailed Overview

The Rugged Monitoring PD201 is a compact design, designed for reliability Partial Discharge (PD) Monitoring Module for Transformers, Switchgears, Power Cables and Rotating Machines. The PD201 PD Monitor combines reliability and user friendly configuration software. It has two variants, 04 channel and 08 channels, that can connect to 4 and 8 PD sensors respectively. The system can be integrated with wide range of PD sensors such as, HFCT, TEV, Bushing Adaptors, Capacitive Couplers, Acoustic, and Ultrasonic PD sensors. 

The PD201 connects to the HF PD sensors installed at the MV/HV assets. It measures the High Frequency (HF) signals emitted by the PD Faults in HV/MV assets. The HF signals are then analyzed for PD activity and Module categorizes pulses as Internal PD, External PD and Noise Signals. Internal PD signals are captured and stored for further analysis such as PRPD, PD Amplitude, Discharge Rate, and trending. The PD amplitude and discharge rate is sent to the third party system via Modbus (RTU) protocol using built-in serial (RS-485) port. The PRPD data is stored int the module and also sent to third party system via CANBUS protocol using built-in CAN port. There is a dedicated team of experts available for customizing partial discharge monitoring solutions to meet specific customer needs.

Technical Specifications

Number of Channels04 or 08 (Simultaneous acquisition, No Multiplexing)
Sampling Rate100 MS/s per channel
Acquisition Bandwidth0.01 - 100Mhz
Vertical Resolution12-Bit
Noise EliminationBad Pass Filters : User selectable integrated filters with 5Mhz to 25Mhz bandwidth range Software Noise Gating : Advanced denoising algorithms
Data Storage (Memory)MicroSD external memory slot (Up to 2 TB)
Compatible PD SensorsAny High Frequency (HF) PD Sensors (Bushing Adaptors, HFCT, TEV, Capacitive Couplers, Acoustic, Ultrasonic etc.)
Synchronization Inputs2 Inputs (Internal and External)
Serial PortRS-485 with Modbus RTU and Can Port with CANBUS protocol
Configuration PortEthernet Port for configuration
Operating Temperature-30 to 75 °C
Storage Temperature-40 to 85 °C
Dimensions4.92" x 4.92" x 1.89" (125mm x 125mm x 48mm)
Humidity95% Non Condensing
Power Input12 - 24V DC (Default)
Power Consumption15W
# of Relays Outputs01 x Fail Safe Relay for System Failure

Ordering Code

PD201 Product ordering code

Product Drawing

PD201 Drawing