PD211

Ultra-High Frequency PD Monitoring Module-Continuous

Durable and Reliable Partial Discharge Monitoring for Critical Assets

PD211 is a compact and durable module for accurate Partial Discharge (PD) monitoring in essential electrical assets, including Transformers, GIS Circuit Breakers, Switchgear – GIS, MV Panel, and Power Cables. Engineered for reliability, the PD211 provides effective insulation health monitoring to improve safety and system efficiency

Features
  • Compact design with flexible mounting options.
  • 4 or 8 channels for simultaneous PD monitoring.
  • Wide frequency range 
  • Advanced noise elimination with tunable filters.
  • Built-in fail-safe relay system alerts 
Benefits
  • Suitable for OEM-type applications
  • Cost optimized solution 
  • Robust datalogging and Analytics
  • Customer specific applications
  • Advanced noise gating
  • Highly robust
Applications
  • Continuous Online PD
  • Monitoring
  • Multi-Point PD Monitoing
  • GIS Circuit Breakers
  • Power Cables
  • High Voltage AC testing
  • Transformer Monitoring
  • Switchgear – GIS, MV Panel
Technical specifications
Number of Channels

04 or 08 (Simultaneous acquisition, No Multiplexing)

Sampling Rate

360 points per cycle

Acquisition Bandwidth

300MHz – 2000MHz

Noise Elimination

User selectable 4 UHF Band Pass Filters.
1. 440-575 MHz
2. 300- 575 MHz
3. 1100 – 2000 MHz
4. 300-1100 MHz

Data Storage (Memory)

Factory Configured SSD Storage up to 1TB (64GB as standard)

Compatible Software

PD Live Webserver, PD Connect, RM EYE

Compatible PD Sensors

Any Ultra High Frequency (UHF) PD Sensors with bandwidth 300MHz – 2000MHz

Synchronization Inputs

2 Inputs (LV and HV)
LV: 5Vpeak
HV: 100Vrms -240Vrms

Serial Port

RS-485 with Modbus RTU

Communication Ports

Ethernet Port for configuration and protocols (RJ45)

Operating Temperature

-30°C to +40°C

Communication Protocols

IEC61850, Modbus RTU, DNP3, MQTT

PD Sensitivity

-10 dBm to -65 dBm

Storage Temperature

-40°C to 85 °C

Dimensions

187.00 mm x 120 mm x 48 mm

Humidity

95% Non Condensing

Power Input

24- 48 VDC, 50 W Maximum

Product Drawing
Ordering Code
Our Presence Across the Globe

Head Office

CANADA
1415 Frank-Carrel, Suite
230, Quebec, QC – G1N
4N7, CANADA