POWER SUPPLY |
24 - 48 Vdc (Default), 125 Vac/Vdc, and any other (upon request) |
|
CPU MODULE |
Data Storage Capacity |
Logging Rate |
Config port |
MicroSD external memory slot (up to 2 TB) |
1 sec interval on USB |
USB (to use with Rugged connect windows software) |
|
SYSTEM CAPACITY |
Maximum number of Channels |
Expandable to 256 Channels, Daisy chain up to 32 units(with Modbus, Canbus) |
|
FIBER OPTIC MODULES |
No of Channels |
Measurement Range |
Resolution |
Accuracy |
Scan Rate |
2, 4, 6 and 8 channels |
-80 °C to +300 °C (cryogenic 4 °K range optional) |
0.1 °C |
±1.0 °C (±0.2 °C in relative temperature) |
200 ms / channel ( Optional: Faster scanning rates available) |
|
ANALOG INPUT MODULE |
No of Input Channels |
AC Current Input |
DC Current Input |
Temperature Input |
Potentiometer |
05 or 10 Channels |
Clamp-on CT with different ranges: 5Amp, 10Amp, 20Amp, 100Amp and others available |
4 - 20 mA |
100 ohm platinum (Pt100) |
up to 20,000 ohms |
|
POWER MONITORING MODULE |
No of Input Channels |
Current Input Range |
Voltage Input Range |
Sampling Rate |
Measurement Parameters |
03 Current and 03 Voltage |
0 - 5A |
0 - 250V |
32 KS/s |
Power, Through-Fault, Motor Torque etc. |
|
DIGITAL INPUT MODULE |
No of Input Channels |
Dry Contact |
Powered Contact |
08 or 16 Channels |
Resistance between the contact < 100 |
75 - 250Vdc |
|
ANALOG OUTPUT MODULE |
No of Input Channels |
Output format |
08 or 16 Channels |
4-20 mA or 0-5V or 0-10VConfigurable for any measured / calculated value |
|
BUSHING MONITORING MODULE |
No of Input Channel |
Leakage Current Range |
Monitoring Parameters |
03 or 06 Channels |
1mA to 200mA |
Tan Delta (PF), Capacitance, Phase Voltage |
|
PARTIAL DISCHARGE MODULE |
No of Input Channels |
Acquisition Bandwidth |
Monitoring Parameters |
04 or 08 Channels |
HPM: 0.01 - 100Mhz UPM: 100 MHz - 2 GHz |
PD Amplitude, Discharge Rate and PRPD |
|
OUTPUT RELAY MODULE |
|
COMMUNICATION OPTIONS |
Ethernet Ports (RJ-45 & FO Ethernet) |
Serial Port |
CANBUS Port |
Modbus, DNP3.0, IEC 60870-5-104, MQTT, IEC61850, PRP |
RS485 with Modbus support |
CANBUS Master/Slave support for Can Dataloggers |
|
EMC COMPLIANCE |
Conducted & Radiated Emissions |
ESD and EM Field Immunity |
Fast Transient & Surge Immunity |
Magnetic Field Immunity |
Immunity from Conducted Disturbances |
Ripple, Dips & Damped Oscillatory |
Safety |
ICES-003 (2016), CISPR32 (2015), CISPR11 (2015) |
IEC61000-4-2, C37.90-3, IEC61000-4-3, C37.90.2 |
IEC61000-4-4, IEC61000-4-5, C37.90.2 |
IEC61000-4-8, IEC61000-4-10 |
IEC61000-4-6, IEC61000-4-16 |
IEC61000-4-17, IEC61000-4-18, IEC61000-4-29 |
IEC60255-26 and CE Certified |
|
ENVIRONMENTAL AND MECHANICAL |
Operating Temperature |
Operating Humidity |
Storage Temperature |
Dimensions 8 Chaise |
Weight |
-40 to 72 °C |
95% Non Condensing |
-40 to 85 °C |
W48.25 x H15.71 x D17.73 cm (19.00" x 2.25" x 6.98") |
App. 5Kg. (for complete filled Chassis) |
|